diesel generator set mtu 12v4000 ds1550 s tand by p o wer : 1550 kw el 380v/60 hz/water charge air cooling/fuel consumption optimized p roduct h ighlights optional equipment and fnishing shown. standard may vary. // benefts - low fuel consumption - optimized system integration ability - high reliability - high availability of power - long maintenance intervals // mtu onsite energy is a single-source supplier // support - global product support offered // standards - engine-generator set is designed and manufactured in facilities certifed to standards iso 2008:9001 and iso 2004:14001 - generator set complies to iso 8528 - generator meets nema mg1, b s5000, iso, din en and ie c standards - nfpa 110 // power rating - system rating: 650 kva - 1700 kva - accepts rated load in one step per nfpa 110 - generator set complies to g3 according to iso 8528-5 - generator set exceeds load steps according to iso 8528-5 // performance assurance certifcation (pac) - engine-generator set tested to iso 8528-5 for transient response - 85% load factor - verifed product design, quality and performance integrity - all engine systems are prototype and factory tested // complete range of accessories available - c ontrol panel - fuel system - fuel connections with shut-off valve mounted to base frame - starting/charging system // emissions - fuel consumption optimized // certifcations - c e certifcation option
2 /// / mtu 12v4000 ds1550 / fc / 60 hz / 380v applic ation data ? // engine manufacturer mtu model 12v4000g43 type 4-cycle arrangement 12v displacement: l 57.2 b ore: mm 170 stroke: mm 210 c ompression ratio 16.4 rated speed: rpm 1800 engine governor adec (ecu 7) max power: k wm 1736 air cleaner dry // fuel system maximum fuel lift: m 5 total fuel fow: l/min 16 // fuel consumption ? l/hr g/kwh at 100% of power rating: 420.4 201 at 75% of power rating: 312.2 199 at 50% of power rating: 221.7 212 // liquid capacity (lubrication) total oil system capacity: l 260 engine jacket water capacity: l 160 intercooler coolant capacity: l 40 // combustion air requirements c ombustion air volume: m 3 /s 2.3 max. air intake restriction: mbar 50 // cooling/radiator system c oolant fow rate (ht circuit): m 3 /h 67 c oolant fow rate (lt circuit): m 3 /h 35 heat rejection to coolant: k w 640 heat radiated to charge air cooling: k w 410 heat radiated to ambient: k w 75 // exhaust system exhaust gas temp. (after turbocharger): c 430 exhaust gas volume: m 3 /s 5.4 maximum allowable back pressure: mbar 85 minimum allowable back pressure: mbar 30 ? all data refers only to the engine and is based on iso standard conditions (25 c and 100m above sea level). ? values referenced are in accordance with iso 3046-1. c onversion calculated with fuel density of 0.83 g/ml. all fuel consumption values refer to rated engine power.
3 /// / mtu 12v4000 ds1550 / fc / 60 hz / 380v // engine 4-c ycle standard single stage air flter oil drain extension & shut-off valve c losed crankcase ventilation governor-electronic isochronous c ommon rail fuel injection fuel consumption optimized engine // generator nema mg1, b s5000, iso, din en and ie c standards self-ventilated superior voltage waveform solid state, volts-per-hertz regulator no load to full load regulation 0.25% voltage regulation no load to full load b rushless alternator with brushless pilot exciter 4 pole, rotating feld sustained short circuit current of up to 300% of the rated current for up to 10 seconds marathon low voltage generator represents standard features ? represents optional features s tandard and o ptional f eatures // system ratings (kw/kva) mtu 12v4000 ds1550 standby power voltage: v 380 phases 3 frequency: hz 60 power output: k w el 1550 power output: kva* 1938 rated amps 2944 generator model marathon 744rsl7091 * cos phi = 0,8 // cooling system jacket water pump thermostat(s) w ater charge air cooling ? jacket water heater
4 /// / mtu 12v4000 ds1550 / fc / 60 hz / 380v // control panel pre-wired control cabinet for easy application of customized controller (v1+) ? island operation (v2) ? automatic mains failure operation with ats (v3a) ? automatic mains failure operation incl. control of generator and mains breaker (v3b) ? island parallel operation of multiple gensets (v4) ? automatic mains failure operation with short (< 10s) mains parallel overlap synchronization (v5) ? mains parallel operation of a single genset (v6) ? mains parallel operation of multiple gensets (v7) ? b asler controller ? deif controller c omplete system metering digital metering engine parameters generator protection functions engine protection sae j1939 engine e cu communications parametrization software multilingual capability multiple programmable contact inputs multiple contact outputs event recording ip 54 front panel rating with integrated gasket ? different expansion modules ? remote annunciator ? daytank control ? generator winding temperature monitoring ? generator bearing temperature monitoring ? differential protection with multi-function protection relay ? modbus rtu-t c p gateway // fuel system flexible fuel connectors mounted to base frame ? fuel filter with water separator ? switchable fuel filter with water separator ? separate fuel cooler represents standard features ? represents optional features s tandard and o ptional f eatures, c ontinuation // exhaust system ? exhaust bellows with connection flange ? y -connection-pipe // mounting system w elded base frame resilient engine and generator mounting modular base frame design // starting/charging system 24v starter ? starter batteries ? b attery rack & cables ? b attery charger
5 /// / mtu 12v4000 ds1550 / fc / 60 hz / 380v subject to change. | 32310221 | edition 01/15 | enc 2015-11. mtu onsite energy a rolls-royce power systems brand www.mtuonsiteenergy.com weights and dimensions sound data // c onsult your local mtu onsite energy distributor for sound data. emissions data // c onsult your local mtu onsite energy distributor for emissions data. r ating definitions and c onditions // standby ratings apply to installations served by a reliable utility source. the standby rating is applicable to varying loads for the duration of a power outage. no overload capability for this rating. ratings are in accordance with iso 8528-1, iso-3046-1, b s 5514 and as 2789. average load factor: 85%. operating hours/year: max. 500. // deration factor: altitude: c onsult your local mtu onsite energy power generation distributor for altitude derations. temperature: c onsult your local mtu onsite energy power generation distributor for temperature derations. rated power is available up to 40 c and 400m above sea level. system dimensions (l x w x h) weight (dry/less tank) open power unit (opu) 4583 x 1836 x 2330 mm 10877 kg materials and specifcations subject to change without notice. w eights and dimensions are based on open power units and are estimates only. c onsult the factory for accurate weights and dimensions for your specifc engine-generator set. drawing above for illustration purposes only, based an standard open power 400 volt engine-generator set. lengths may vary with other voltages. do not use for installation design. see website for unit specifc template drawings.
|