input operating -25% to +30% output voltage voltage range output lvd relay contacts 1 pole changeover - see table for current rating lvd alarm set range -35 to +10% output voltage (user adjustable) pre-warning -35 to +10% output voltage disconnect (user adjustable) general alarm relay contacts 1 pole changeover, 1 a 24 vdc screw terminal sizes input - suitable for 1.0 mm 2 cable, lvd - suitable for 2.5 mm 2 cable, alarms - suitable for 1mm 2 cable mounting din rail environmental operating 0 ? to +50 ? (40 ? ambient plus temperature +10 ? rise inside enclosure) storage -40 ? to +85 ? temperature humidity 90% non-condensing up to 30 a maximum current deep discharge pre-warning alarm din rail mounting automatic reset 12, 24 & 48 vdc up to 30 a lvd series low volt disconnect module specification t he xp erts i n p ower www.xpplc.com sales@xpplc.com mechanical details lvd series output output model voltage current number 12 v 30 a lvd12 24 v 20 a lvd24 48 v 10 a LVD48 notes: 1. all dimensions in mm. 2. weight 0.11 kg. 3. alarm contacts shown in de-energised state. psu lvd schematic note: f2 - max rating 20 a f2 f1 rev 2.0
|